Appendix F (cont'd.)
Object Identifier Object Name Object Type Present Value/Range
Analog Value, 34 Setpoint #6 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 35 Setpoint #7 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 36 Setpoint #8 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 37 Setpoint #9 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 38 Setpoint #10 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 39 Setpoint #11 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 40 Setpoint #12 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 41 Setpoint #13 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 42 Setpoint #14 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 43 Setpoint #15 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 44 Setpoint #16 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 45 Pump # 1 Speed ANALOG_VALUE 0 to 100
Analog Value, 46 Pump # 2 Speed ANALOG_VALUE 0 to 100
Analog Value, 47 Pump # 3 Speed ANALOG_VALUE 0 to 100
Analog Value, 48 Pump # 4 Speed ANALOG_VALUE 0 to 100
Analog Value, 49 Pump # 5 Speed ANALOG_VALUE 0 to 100
Analog Value, 50 Pump # 6 Speed ANALOG_VALUE 0 to 100
Analog Value, 51 Lead Pump Number ANALOG_VALUE 1 to Pump # (in Technologic User Setup Menu)
Analog Value, 52 Active Zone Number ANALOG_VALUE 1 to Zone # (in Technologic User Setup Menu)
Analog Value, 53 Operation Mode ANALOG_VALUE 0=Manual, 1=Auto, 2=Auto Bypass, 3=Manual Bypass
Analog Value, 54 Bypass Valve Position ANALOG_VALUE 0 to 100. (0 = Closed 100 = Open)
Analog Value, 55 Chiller #1 Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 56 Chiller #2 Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 57 Chiller #3 Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 58 Chiller #4 Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 59 Chiller #5 Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 60 Chiller #6 Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 61 Chiller #1 DP ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 62 Chiller #2 DP ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 63 Chiller #3 DP ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 64 Chiller #4 DP ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 65 Chiller #5 DP ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 66 Chiller #6 DP ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)