INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.SAFETYINSTRUCTIONSThis safety alert symbol will be used in this manual and on theTechnologic 5
102.2.2 GroutAfter the frame has been leveled and securely boltedto the pad, a good grade of grout should be installedbeneath the base. A suggested m
113.1 Power-upPut LOCAL-REMOTE-OFF (LRO) switch in theLOCAL position. Put the optional AUTO-OFF-HANDswitch in the AUTO position. Turn main disconnect
From the Technologic Pump Controller screen,shown in section 3.2, press the SETUP/3 key to getto the Setup Selection Menu shown below. Setup Selectio
13Typically the variable value is zero at 4mA for manysensors. An exception would be for a temperaturesensor. Enter the desired zero value by pressi
144.1.12Sensor Setup Exit (not PV)If NO/0 was selected in section 4.1.8 (the sensordoes not provide a PV), the display will show: Sensor No ## (
Table 4: Pump Off Delay Variables15State DescriptionN/A pump not available as defined by setupRdy pump available, not runningOn pump is runningOff pum
164.2.9 Low Load TransferFrom section 4.2, press 4 and ENTER to get to theLow Load Transfer screen shown below. Low Load TransferPoint ### % SpeedEna
17Press NO/0 and ENTER to edit the fields. To returnto the Stage/Destage Menu, shown in section 4.3.1,press YES/7 and ENTER. See Table 8 below for a
18Variable Unit Description Default Value Range Field ValueAFD Fail s Proof timer prior to setting the AFD fail alarm 20 0-999Pr TmPump Fail s Proof
194.3.5 Bypass SetupFrom the System Setup Menu, shown in section 4.3,press F1/LOG/5 and ENTER to get to the BypassSetup screen shown below. No of AFD
2PrefaceThe following manual describes the new microproces-sor based Technologic 5500 Variable Primary PumpController. This unit is in the tradition
204.3.8 Password SetupFrom the System Setup Menu, shown in section 4.3,press F3/INFO/8 and ENTER to get to the PasswordSetup screen shown below. En
214.3.9.2 DOFrom the I/O Setup Menu, shown in section 4.3.9,press SET POINT/2 and ENTER to get to the DOscreen shown below. Total Avail. DO: #Opt. DO
224.3.10 Communication Setup MenuFrom the System Setup Menu, shown in section 4.3,press 10 and ENTER to get to the CommunicationSetup Menu shown below
234.3.10.4 BACnet/IPFrom the Communication Setup Menu, shown in sec-tion 4.3.10, press ALTERNATION/4 and ENTER to getto the BACnet/IP screen shown bel
244.3.14 Load from FlashFrom the System Setup Menu, shown in section 4.3,press 13 and ENTER to get to the Save to Flashscreen shown below. **WARNING*
254.4.7 Disp TestFrom the Test Selection Menu, shown in section 4.4,press YES/7 and ENTER to get to the Disp Test Screenshown below. Press Clear to
26Press the numeric key for the chiller you wish tosetup. The chiller number is limited to the maximumnumber of chillers. Press ENTER to proceed with
274.7 Bypass Valve SetupFrom the Setup Selection Menu, shown in section 4,press YES/7 and ENTER to get to the Bypass ValveSetup Menu shown below. S
28Section 5 - Operation5.1 Status Screens5.1.1 Technologic Pump Controller ScreenThe Technologic Pump Controller screen displays thedate, time, stat
295.1.9 Active Values Seq ScreenPressing NEXT SCREEN, the controller will displaythe Active Values Seq screen shown below.Active ValuesSeq:
3SECTION 1 - GENERAL Page 1.1 Purpose of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30Press the SETUP/3 key followed by ENTER to pro-ceed to manual bypass operation. The display willnow show the following:Technologic Pump ControllerD
315.9AlternationFrom the Technologic Pump Controller screen, shownin section 3.2, press Alternation/4 to get to the Alter-nation screen shown below.
32The following is a description of the hardware, diag-nostics, and corrective action to maintain a processbeing controlled by the Technologic 5500 Va
336.10 Field RepairGeneral - typical field repair should include: replac-ing fuses, replacing input/output modules and assur-ing connections are corr
346.13.3 Data Log MenuFrom the Logging Menu, shown in section 6.13, pressSETUP/3 and ENTER to get to the Data Log Menushown below. Selection : #
356.13.4.4 System Reset LogFrom the Operation Log Menu, shown in section6.13.4, press ALTERNATION/4 and ENTER to get tothe System Reset Log screen sho
36SYSTEM PIPING AND UNITINSTALLATION – FINAL CHECK LIST____ 1. Is the unit base properly level, grouted and secured?____ 2. Are all lubrication points
Appendix C - Valid I/O CodesCode Function Description I/O Type Range Equate to the Signal101 Pump 1 Status (On/Off) DO 1/0 On/Off102 Pump 2 Status (On
38Appendix D - BACnet MS/TP Protocol Implementation Conformance StatementBACnet MS/TP Protocol Implementation Conformance StatementDate: 9/13/06Vendor
39Appendix E - BACnet IP Protocol Implementation Conformance StatementBACnet IP Protocol Implementation Conformance StatementDate: 9/13/06Vendor Name:
4INDEX (continued)4.2.2 Number of Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40Appendix F - BACnet Communications ObjectsObject Identifier Object Name Object Type Present Value/RangeBinary Input, 1 P1 Overload Failure BINARY_IN
41Appendix F (cont'd.)Object Identifier Object Name Object Type Present Value/RangeBinary Input, 59 AI #9 Failure BINARY_INPUT 1 = Failure
42Appendix F (cont'd.)Object Identifier Object Name Object Type Present Value/RangeAnalog Value, 34 Setpoint #6 ANALOG_VALUE 0 to Span (in Techno
43Appendix G - LonWorks Communications PointsSNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit0 nvoPmp1_OL_Fail SNVT_switc
44Appendix G (cont'd.)SNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit47 nvoPmp5_On_Off SNVT_switch(95) 2 Pump #5 On
45Appendix G (cont'd.)SNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit94 nvo_KW1 SNVT_power_kilo (15) 2 KW #1 0 to S
46Appendix G (cont'd.)SNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit141 nviSeq_Alt SNVT_switch(95) 2 Pump Sequence
47Appendix H - Metasys N2 Communications PointsNPT NPA POINT DESCRIPTION RANGE/VALUE UNITBI 1 Pump #1 Overload Failure 1 = Failure 0 = O.K.BI 2 Pump
48Appendix H (cont'd.)NPT NPA POINT DESCRIPTION RANGE/VALUE UNITBI 50 System Start/Stop 1 = Start 0 = StopBI 51 Analog Input #1 Fai
49Appendix H (cont'd.)NPT NPA POINT DESCRIPTION RANGE/VALUE UNITADI 19 System KW 0 to Span (in Technologic User Setup Menu) KWADI 20 Pump #1 Pow
5INDEX (continued)5.2 Bypass Valve Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50Appendix I - Modbus RTU Communications PointsFunction ModbusCode Point # Point Description Range/Value Address Unit02 1 Pump #1 Overload Failure 1 =
51Appendix I (cont'd.)Function ModbusCode Point # Point Description Range/Value Address Unit02 51 Analog Input #1 Failure 1 = Failure 0
52Appendix I (cont'd.)Function ModbusCode Point # Point Description Range/Value Address Unit04 19 System KW 0 to Span (in Technologic User Setup
53Appendix J – DrawingsDrawing # Description1 Technologic 5500 Variable Primary Pump Controller – Door2 Technologic 5500 Variable Primary Pump Control
4 LINE DISPLAYNUMERIC KEY PADFUNCTION KEYS WITH LEDSTechnologic 5500 Operator Interface and CPUDRAWING 3.0Xylem Inc. 10661 Newkirk Street Dallas, TX 7
6NOTE: The information contained in this manual is intended to assist operating personnel by providing information on the char-acteristics of the purc
71.1Purpose of ManualThis manual is furnished to acquaint you with someof the practical ways to install, operate, and maintainthis unit. Read it caref
81.7 Ground ConnectionsA grounding terminal is provided for a dedicatedground wire connection. All provisions of theNational Electrical Code and loca
91.12.4 Analog Inputs with External PowerThe following steps describe the general procedurefor rewiring an analog input sensor when the sensor'sp