13
Typically the variable value is zero at 4mA for many
sensors. An exception would be for a temperature
sensor. Enter the desired zero value by pressing the
appropriate numeric keys followed by the ENTER
key.
4.1.8
Sensor PV
The display will now show the following:
Sensor No ## (Type)
Span = ##### Zero = #####
PV: ? (Y/N)
Press the YES/7 key if the selected sensor will con-
trol the system by supplying a process variable feed-
back signal. Typical process variable signals are
supplied by one of the following: Pressure, Differ-
ential Pressure, Temperature, or Differential Tempera-
ture sensors. Continue to section 4.1.9
Press the NO/0 key for all sensors that supply option-
al signals. Typical optional signals are supplied by
any of the following: System Differential Pressure,
System Differential Temperature, Flow, and KW
Sensors. If NO/0 was selected, skip to section 4.1.12.
4.1.9
Sensor Set Point
If YES was selected in section 4.1.8, the display will
now prompt the user for a Set Point NO as shown
below.
Sensor No ## (Type)
Span = ##### Zero = #####
PV: Y Set Point No: ##
Enter a setpoint number by using the numeric key-
pad. See section 5.8 for more information on how to
modify setpoints.
4.1.10
Sensor Override
The display will now show:
Sensor No ## (Type)
Span = # Zero = #
PV: Y/N Set Point No: ##
Override: Y/N
The controller is capable of accepting sensor input
either through a 4-20mA analog input or through the
RS-485 communication port. The communication
port must be set up properly and connected to an
external building automation system.
Press the YES/7 key to receive the sensor signals via
the RS-485 port. Press the ENTER key.
Press the NO/0 key to receive the sensor signals via
the analog input card. Press the ENTER key
4.1.11
Sensor Setup Exit
The display will now show:
Sensor No ## (Type)
Span = # Zero = #
PV: Y/N Set Point No: ##
Override: Y/N Ok? (Y/N)
If correct, record your sensor setup information on
the wiring diagram that was included with the unit.
Press YES/7 and then ENTER to accept all of the
values shown and return to section 4.1.4.
Press NO/0 and ENTER to return to section 4.1.5 and
modify the sensor.
Selection Description Units
1=DP Differential Pressure PSID
2=PR Pressure PSI
3=Flow Flow Rate GPM
4=KW Power, from each AFD, totalized in controller. KW
5=Temp Temperature °F
6=Delta T Differential Temperature °F
7=SysDP System Differential Pressure PSID
8=SysKW System Power, from KW transmitter at single point power connection KW
*9=Chi Flow Chiller Flow GPM
*10=Chi DP Chiller Differential Pressure PSID
11=S Temp System Temperature °F
12=R Temp Return Temperature °F
13=BYP V FB Bypass Valve Feedback %
0=None Non-standard transmitter N/A
Table 2: Sensor Types